  1description axioline ? f power module for the communications power u bus , max. 4 a axl f pwr 1h ? phoenix contact data sheet the module is designed fo r use within an axioline ? f station. if the maximum load of the bus coupler for the axioline ? f local bus supply (communications power u bus ) is reached, this module can be used to provide this voltage again. to this end, apply a 24 v dc voltage (u l ) to the module from which the (u bus ) is generated. features ? supply of the 24 v voltage u l for generating the communications power u bus ? diagnostic and status indicators this module does not have a microprocessor and is therefore not a local bus device. it is not mapped to engineering tools. note: malfunction the power module only boosts the u bus voltage, if the corresponding red bus base module is snapped on and if the u bus voltage is present in the segment downstream of the power module. this data sheet is only valid in association with the um ? en ? axl ? f ? sys ? inst user manual. make sure you always use the latest documentation. it can be downloaded from the product at phoenixcontact.net/products . 105688_en_02 2016-03-02
axl f pwr 1h 105688_en_02 phoenix contact 2 / 6 2table of contents 1 description ................................................................................................................... ........... 1 2 table of contents ............................................................................................................. ........ 2 3 ordering data ................................................................................................................. ......... 3 4 technical data ................................................................................................................ ......... 3 5 internal circuit diagram ...................................................................................................... ...... 5 6 terminal point assignment..................................................................................................... .. 5 7 connection example............................................................................................................ .... 5 8 installation instructions ..................................................................................................... ....... 5 9 local diagnostic and status indicators ..................................................................................... 6
axl f pwr 1h 105688_en_02 phoenix contact 3 / 6 description ty p e order no. pcs./pkt. axioline ? f power module for the commun ications power ubus, max. 4 a (including bus base module and connector) axl f pwr 1h 2688297 1 3ordering data accessories ty p e order no. pcs./pkt. axioline ? f bus base module for power modules in housing type h (replacement item) axl f bs h pwr 2702051 5 axioline ? f short power connector (for e.g., axl ? f ? bk ...) (replacement item) axl cn s/ul 2701421 5 zack marker strip for axioline ? f (device labeling), in 2 x 20.3 mm pitch, unprinted, 25-section, for individual labeling with b-stift 0.8, x-pen, or cms-p1-plotter (marking) zb 20,3 axl unprinted 0829579 25 zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual labeling with m-pen 0,8, x-pen, or cms-p1-plotter (marking) zbf 10/5,8 axl unprinted 0829580 50 insert label, roll, white, unlabele d, can be labeled with: thermomark roll, thermomark roll x1, thermomark x, thermomark s1.1, mounting type: snapped into marker carrier, lettering field: 35 x 28 mm (marking) emt (35x28)r 0801602 1 documentation ty p e order no. pcs./pkt. user manual, english, axioline ? f: system and installation um en axl f sys inst - - dimensions (nominal sizes in mm) width 35 mm height 126.1 mm depth 54 mm note on dimensions the depth is valid when a th ? 35-7.5 din rail is used (according to en ? 60715). 4 technical data 35 54 122,4 125,9 general data color traffic grey a ral 7042 weight 107 g (with connector and bus base module) ambient temperature (operation) -25 c ... 60 c ambient temperature (storage/transport) -40 c ... 85 c permissible humidity (operation ) 5 % ... 95 % (non-condensing) permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
axl f pwr 1h 105688_en_02 phoenix contact 4 / 6 air pressure (operation) 70 kpa ... 106 kpa (up to 3000 m above sea level) air pressure (storage/transport) 70 kpa ... 106 kpa (up to 3000 m above sea level) degree of protection ip20 protection class iii, iec 61140, en 61140, vde 0140-1 mounting position any (no temperature derating) general data connection data designation axioline ? f connector connection method push-in connection conductor cross section solid / stranded 0.2 mm2 ... 1.5 mm2 / 0.2 mm2 ... 1.5 mm2 conductor cross section [awg] 24 ... 16 stripping length 8 mm please observe the information provided on conductor cross sections in the ?axioline ? f: system and installation? user manual. interface axioline ? f ? local bus connection method bus base module transmission speed 100 mbit/s communications power supply of communications power u l 24 v dc maximum permissible voltage range 19.2 v dc ... 30 v dc (including all tolerances, including ripple) current supply at u bus max. 4 a current consumption from u l max. 1.2 a (i bus = 4 ? a; u l = 19,2 ? v) power consumption at u l max. 22 w (i bus = 4 a) note: damage to the electronics provide the module with an external fuse to protect it against polarity reversal. the power supp ly unit must be able to supply four times the nominal current of the external fuse, to ensu re that it trips in the event of an error. error messages to the higher level control or computer system none mechanical tests vibration resistance in acc. with en ? 60068-2-6/iec ? 60068-2-6 5g shock in acc. with en ? 60068-2-27/iec ? 60068-2-27 30g continuous shock according to en ? 60068-2-27/iec ? 60068-2-27 10g conformance with emc directive 2004/108/ec (valid un til 19.04.2016) / 2014/30/eu (valid from 20.04.2016) noise immunity test in accordance with en 61000-6-2 electrostatic discharge (esd) en ? 61000-4-2/iec ? 61000-4-2 criterion b, 6 kv contact discharge, 8 kv air discharge electromagnetic fields en ? 61000-4-3/iec ? 61000-4-3 criterion a; field intensity: 10 v/m fast transients (burst) en ? 61000-4-4/iec ? 61000-4-4 criterion b, 2 ? kv transient overvoltage (surge) en ? 61000-4-5/iec ? 61000-4-5 criterion b, dc supply lines: 0 .5 kv/0.5 kv (symmetrical/asymmetrical) conducted interference en ? 61000-4-6/iec ? 61000-4-6 criterion a; test voltage 10 v noise emission test according to en 61000-6-3 radio interference properties en 55022 class b approvals for the latest approvals, please visit phoenixcontact.net/products.
axl f pwr 1h 105688_en_02 phoenix contact 5 / 6 5 internal circuit diagram figure 1 basic circuit diagram key: the module disconnects the in coming voltage routing for u bus and re-establishes it for the subsequent modules. 6 terminal point assignment figure 2 terminal point assignment 7 connection example figure 3 connection of the cables 8 installation instructions the bus base module belonging to the power module is red. as such, it differs from all other bus base modules. the bus base module is coded in such a way that it cannot accommodate any other modules. local bus axioline ? f local bus (hereinafter referred to as local bus) diag circuit diagnostics circuit power supply unit led electrically isolated areas ul e1 u 2 4 v l u bus 2 4 v diag circuit u l e1 u bus u bus gnd bus xxx xxx te r m i n a l point color assignment supply voltage input a1, a2 red 24 v dc (u l ) supply of the logic voltage (internally jumpered) b1, b2 blue gnd reference potential of the supply voltage (internally jumpered) note: malfunction ensure you insert the power module into the associated bus base module! if you use an incorrect bus base module both leds will illuminate red and the power module will be inoperative. a1 a2 b1 b2 a1 a 2 b1 b 2 24 v d c ( u ) l + -
axl f pwr 1h 105688_en_02 6 / 6 phoenix contact gmbh & co. kg ? 32823 blomberg ? germany phoenixcontact.com 9 local diagnostic and status indicators figure 4 local diagnostic and status indicators ul e1 designati on color meaning state description ul green/red u l ogic green on communications power u bus is present. red on communications power u bus is not present or overloaded. communications power u bus downstream of the power module is not present. off communications power supply not present. e1 red error red on module has been snapped on to the wrong bus base. off module has been snapped on to the right bus base.